Input Measurment Display |
Network | Three-phase three-wire, Three-phase four-wire | |
Voltage | Rating | AC100V,400V(Please specify when ordering) | |
Overload | Continuous: 1.2 times instantaneous: 2 times | ||
Power consumption | <1VA(each phase) | ||
Resistance | ≥500kΩ | ||
Precision | RMS measurement,Accuracy level 0.2/0.5 | ||
Current | Rating | AC1A,5A(Please specify when ordering) | |
Overload | Continuous: 1.2 times instantaneous: 2 times | ||
Power consumption | <0.4VA(each phase) | ||
Resistance | <2mΩ | ||
Precision | RMS measurement,Accuracy level 0.2/0.5 | ||
Frequency | 40~60Hz,accuracy 0.1Hz | ||
Power | Active, reactive, accuracy 0.2/0.5 | ||
Electric Energy | Energy metering,Active accuracy 0.2/0.5,Inactive accuracy 1.0 | ||
Display | Programmable, switching, loop (LCD/LED) display | ||
Power | Working Scale | AC220V or AC/DC85~265V(optional) | |
Consumption | ≤5VA | ||
Output | Communication Interface | Rs485 | |
Pulse output | 2-way energy pulse output, optocoupler isolation | ||
Ambient | Ambient | 10~55℃ | |
Storage environment | -20~70℃ | ||
Safety | Withstand voltage | Input/Power>2kV Power/Output>1kV | |
Insulation | Input,Output,Power on the machine>50MΩ | ||
Dimension | 96mm*96mm*85mm |